Mid-Temperature Self-Regulating Heating Cable (SLMCBL)
Cut-to-length mid-temperature self-regulating heating cable (SLMCBL) is ideal for freeze protection and mid temperature process maintece up to 230F (110C). Self-regulating heating trace cable self-regulates temperature by automatically adjusting heat output based on surface and ambient temperatures. Choose between three different outer layers for dry, wet, or harsh environments. No temperature controller is required. Note: Special consideration must be given for the circuit breaker due to the high-initial in-rush currents
- Fluropolymer Jacket
- 15 W/ft (45 W/m)
- 120V
Since 1949
Additional Features:
- Safe to overlap and insulate
- Can be cut-to-length and terminated in the field
- Moisture, chemical, and glame resistant
Specifications:
- Maximum Continuous Maintenance Temperature: 230°F (110°C)
- Intermittent Exposure Temperature Range: -22°F to 275°F (-30°C to 135°C)
- Nominal Power Output at 50°F (10°C): 5, 10, 15, 20 W/ft, (16, 33, 49, 66 W/m)
- Supply Voltages: 110-120 VAC or 208-277 VAC
- Bus Wire Gauge:16 AWG
- Braid Resistance: Tinned copper 0.0055 ohms/ft (0.0182 ohms/m)
- Bend Radius: 0.5 in (12 mm)
Outer Layer Options:
|
Product Type |
Description |
Nominal Dimensions |
Shipping Weight: 500-ft (152m) spool |
Purpose |
|
SLMCBL-B |
Tinned Copper Metal Braid |
0.15” x 0.45” (3.8mm x 11.4mm) |
32 lb. (14.5 kg) |
Dry |
|
SLMCBL-BP |
Tinned Copper Metal Braid with Thermoplastic Elastomer Overjacket |
0.23” x 0.54” (6.0mm x 13.6mm) |
37 lb. (16.8 kg) |
Wet or Weak |
|
SLMCBL-BF |
Tinned Copper Metal Braid with Fluoropolymer Overjacket |
0.19” x 0.49” (4.8mm x 12.4mm) |
47 lb. (21.2 kg) |
Wet or Harsh |
| PART NUMBER | VOLTAGE | WATTS PER FOOT (METER) | OUTER COVER |
|---|---|---|---|
| SLMCBL5120B | 110-120 | 5 W/ft (17 W/m) | Tinned Copper Metal Braid |
| SLMCBL5120BP | 110-120 | 5 W/ft (17 W/m) | Thermoplastic Overjacket |
| SLMCBL5120BF | 110-120 | 5 W/ft (17 W/m) | Fluoropolymer Overjacket |
| SLMCBL10120B | 110-120 | 10 W/ft (31 W/m) | Tinned Copper Metal Braid |
| SLMCBL10120BP | 110-120 | 10 W/ft (31 W/m) | Thermoplastic Overjacket |
| SLMCBL10120BF | 110-120 | 10 W/ft (31 W/m) | Fluoropolymer Overjacket |
| SLMCBL15120B | 110-120 | 15 W/ft (45 W/m) | Tinned Copper Metal Braid |
| SLMCBL15120BP | 110-120 | 15 W/ft (45 W/m) | Thermoplastic Overjacket |
| SLMCBL15120BF | 110-120 | 15 W/ft (45 W/m) | Fluoropolymer Overjacket |
| SLMCBL20120B | 110-120 | 20 W/ft (60 W/m) | Tinned Copper Metal Braid |
| SLMCBL20120BF | 110-120 | 20 W/ft (60 W/m) | Fluoropolymer Overjacket |
| SLMCBL5240B | 208-277 | 5 W/ft (17 W/m) | Tinned Copper Metal Braid |
| SLMCBL5240BP | 208-277 | 5 W/ft (17 W/m) | Thermoplastic Overjacket |
| SLMCBL5240BF | 208-277 | 5 W/ft (17 W/m) | Fluoropolymer Overjacket |
| SLMCBL10240B | 208-277 | 10 W/ft (31 W/m) | Tinned Copper Metal Braid |
| SLMCBL10240BP | 208-277 | 10 W/ft (31 W/m) | Thermoplastic Overjacket |
| SLMCBL10240BF | 208-277 | 10 W/ft (31 W/m) | Fluoropolymer Overjacket |
| SLMCBL15240B | 208-277 | 15 W/ft (45 W/m) | Tinned Copper Metal Braid |
| SLMCBL15240BP | 208-277 | 15 W/ft (45 W/m) | Thermoplastic Overjacket |
| SLMCBL15240BF | 208-277 | 15 W/ft (45 W/m) | Fluoropolymer Overjacket |
| SLMCBL20240B | 208-277 | 20 W/ft (60 W/m) | Tinned Copper Metal Braid |
| SLMCBL20240BF | 208-277 | 20 W/ft (60 W/m) | Fluoropolymer Overjacket |