SLM Mid-Temperature Self-Regulating Heating Cable
Click to Enlarge
Click to Enlarge
Click to Enlarge
|
Product Highlights
Automatically adjusts heat output based on surface temperature
No temperature controller is necessary*
Can be safely overlapped and insulated
Ideal for freeze protection and low temperature process maintenance
* If a specific process temperature is required, a temperature controller is necessary.
Specifications
- Maximum exposure temperature is 250°F (121°C)
- 5, 10, 15 watts/ft
- Moisture, chemical, and flame resistant
- 16AWG bus wires
- T-Rating: T3**
** Electrical equipment T-rating codes define the maximum surface temperature that equipment will reach. It is used in hazardous (classified) area applications.
Approvals
US LISTED |
![]() |
![]() |
|
Ordinary Locations Hazardous (Classified) Locations Class
I, Division 2, Groups A, B, C, D Class II, Division 2, Groups F, G
Class III, Division 2 |
Ordinary Locations Hazardous (Classified) Locations Class
I, Division 2, Groups B, C, D
Class II, Division 2, Groups E, F, G |
Ordinary Locations Hazardous
(Classified) Locations Class I, Division 2, Groups B, C, D Class II and III, Division 2, Group G |
Approvals valid only when used with appropriate heating cable
and installation accessories, and installed in accordance with all applicable instructions,
codes, and regulations.
Outer Layer Options
| Product Type | Description | Dimensions | Shipping weight per 500-foot (152m) spool | Purpose |
| SLM-B | Tinned Copper Metal Braid |
0.15" x 0.40" (4mm x 10mm) |
40 lb. (18kg) | Ordinary applications |
| SLM-BF | Tinned Copper Metal Braid with Fluoropolymer Overjacket |
0.20" x 0.40" (5mm x 10mm) |
48 lb. (22kg) | For use in strong chemical environments (i.e. strong acids) |
Maximum Circuit Length in Ft vs. Circuit Breaker Size
| Heat Cable Type | Circuit Breaker Size | Maximum Length (ft) | |
| 120VAC | 120VAC | ||
| SLM-5 |
15 amp 20 amp 30 amp |
185 245 310 |
385 500 620 |
| SLM-10 |
15 amp 20 amp 30 amp |
115 150 190 |
225 300 375 |
| SLM-15 |
15 amp 20 amp 30 amp |
80 110 135 |
160 215 270 |
- Special consideration must be given for the circuit breaker due to the high initial in-rush currents.
- Maximum lengths are based on start-up temperatures between -20°F to 50°F (-29°C to 10°C)
Voltage Adjustment
| Adjustment Multiplier | ||||||
| Product Type | 208 VAC | 220 VAC | 277 VAC | |||
| Power | Length | Power | Length | Power | Length | |
|
SLM-5-240 SLM-10-240 SLM-15-240 |
0.76 0.80 0.83 |
0.93 0.93 0.93 |
0.85 0.88 0.89 |
0.96 0.96 0.96 |
1.29 1.23 1.19 |
1.07 1.07 1.02 |
SLM Mid-Temperature Self Regulating Heating Cable Specification Sheet
Ordering Information
Part Number Matrix
![]() Click to Enlarge |
Connection / Termination Kits
| Part Number | Kit | Enough to Complete |
| SLUC-1 | Universal Connection Kit | Two end terminations and one input connection, or one input power splice. Good for any heating cable smaller than 0.44" (11mm) diameter. Note: Requires a junction box. |
| SLSK-5 | In-Line Splice/Tee Splice Kit | Five in-line splices or Five tee splices. |
| SLET-2 | End Seal Kit | Two end terminations. |
| SLPT-2 | Power End Termination Kit | Two power terminations. |
| MLK | End of Circuit Light Kit | Provides a LED end of circuit indication for SL and SLM heating cables. |
| SLJB-2 | Junction Box | Non-Metalic junction box, 5" x 5" x 2" (127mm x 127mm x 51mm), NEMA 4X. Recommended for SLRPC-1 and SLUC-1. |
Click Here for details and contents
of SLM Connection / Termination Kits
Accessories
![]() |
Adhesive Tape Helps to isolate the cable from the insulation and provides intimate contact with surface to be heated.
|
![]() |
Caution Label Required by code for every 100ft (3m) of pipe.
|
![]() |
Heat Conductive Putty Used to fill voids between cable and pipe surface.
|
![]() |
Insulation Cost effective, flexible thermal insulation for pipes and vessels. |
![]() |
Junction Box (SL and SLM Cable) Non-Metalic Junction box. Recommended for SLUC-1 and SLRPC-1 Kits
|
![]() |
RTV Sealant Silicone sealant used to seal lead pouches, end pouches, and pipe standoffs.
|
![]() |
Pipe Strap Stainless steel pipe straps used to secure pipe standoff to pipe.
|
Support
Documents>
SLM Mid-Temperature Self Regulating Heating Cable Specification Sheet
Self Regulating Heating Cable Selection Guide
Guide for Calculating Length and Type of Heating Cable Needed
Examples of Heating Cable Placement
SLM Connection / Termination Kits
Heating Cable Accessories
Instruction Manuals
SL Self Regulating Heating Cable Installation & Maintenance Instructions
SLUC-1 Universal Connection Kit Installation Instructions
SLSK-5 In-Line Splice-Tee Splice Kit Installation Instructions
SLET-2 End Seal Kit Installation Instructions
SLPT-2 Power End Termination Kit Installation Instructions
MLK End of Circuit Light Kit Installation Instructions


Click to Enlarge
Click to Enlarge
Click to Enlarge










Save to Favorites
Print this Page