FE General Purpose Constant-Wattage Heating Cable
![]() Click to Enlarge
Click to Enlarge
|
Product Highlights
Temperatures up to 400°F (204°C)
Power remains constant regardless of temperature
Can be cut-to-length at job site
Ideal for a wide range of general purpose applications
- Mid-range process temperature control for food and chemical processing
- Water lines
- Fire protection systems
- Fuel oil
- Condensate return
- Hot water lines
- Lines periodically purged with 250 psig steam
Specifications
- Maximum exposure temperature is 400°F (204°C)
- Moisture, chemical, flame, and radiation resistant
- 12AWG bus wires
- Dimensions 0.2" x 0.3" (5 x 8mm)
- 40 lb. (18kg) per 500-foot (152m) spool
TEFLON® is a registered Trademark of DuPont used under license.
Approvals
Ordinary Locations
Hazardous Location (T3 rated):
Class I Division 2 Groups B, C, D
Class II Division 2 Groups F, G
Class III Division 2
, Ordinary locations (120 and 240VAC)
Approval valid only when used with appropriate heating cable and installation accessories, and installed in accordance with all applicable instructions, codes, and regulations.
|
Maximum Circuit Length in ft (m)
|
Circuit Module Length in ft (m)
Note: when ordering, please allow a minimum of 1 module length extra for terminations. |
FE General Purpose Constant-Wattage Heating Cable Specification Sheet
Ordering Information
Part Number Matrix

Connection / Termination Kits
| Part Number | Kit | Enough to Complete |
| FECABUC | Universal Connection / Termination Kit | Two end terminations and one input connection, or one power input splice. Note: Requires a double hub junction box. |
| FECABKC | Lead / End Seal Kit | Five lead and end terminations. |
| FECABSK | Splice Kit | One in line splice or one tee splice. Note: Requires pipe standoff, pipe straps, single hub junction box, and RTV sealant. |
| FECABLP | Lead Termination Kit | One lead termination. |
| FECABEP | End Termination Kit | One end termination. |
FE Connection / Termination Kit Specification Sheet
Temperature Controller
A temperature controller is required for this product. Check out temperature controller section for a complete selection of temperature controllers.
Accesories
![]() |
Adhesive Tape Helps to isolate the cable from the insulation and provides intimate contact with surface to be heated.
|
![]() |
Caution Label Required by code for every 100ft (3m) of pipe.
|
![]() |
Heat Conductive Putty Used to fill voids between cable and pipe surface.
|
![]() |
Monitor Light Kit Provides a continuity check at the termination end of a cable circuit.
|
![]() |
Pipe Reducer
|
![]() |
Pipe Standoff Cast aluminum fitting.
|
![]() |
Pipe Strap Stainless steel pipe straps used to secure pipe standoff to pipe.
|
![]() |
RTV Sealant Silicone sealant used to seal lead pouches, end pouches, and pipe standoffs.
|
Support
Documents
FE Constant-Watt Heating Cable Specification Sheet
Part # 11467: FE Constant-Watt Heating Cable Instruction Manual
Constant-Watt Heating Cable Selection Guide
Guide for Calculating Length and Type of Heating Cable Needed
Examples of Heating Cable Placement
FE Connection / Termination Kits
Heating Cable Accessories











Save to Favorites